Gold Member Since 2010
Audited Supplier
Zhejiang Cen New Energy Technology Co., Ltd.

Low Temperature Heat Pump, Heat Pump, Air to Water Heat Pump manufacturer / supplier in China, offering Evi Low Temperature Air Source Heat Pump Lowest Working Temp. -25c, Tested in National Proved Laboratory, Swimming Pool Air Source Heat Pump for Hot Water-3p, Air Source Home Use Heat Pump 3.5kw (Static) -200L Water Tank and so on.

(/ )

Supplier Homepage Product EVI system air source heat pump Evi Low Temperature Air Source Heat Pump Lowest Working Temp. -25c, Tested in National Proved Laboratory

Evi Low Temperature Air Source Heat Pump Lowest Working Temp. -25c, Tested in National Proved Laboratory

Purchase Qty.:
(Pieces)
1-9 10+
FOB Unit Price: US $1,550 US $1,400
Purchase Qty. (Pieces) FOB Unit Price
1-9 US $1,550
10+ US $1,400
Get Latest Price
Production Capacity: 2000 Units/Month
Transport Package: Safe Export Packing, With Pallet
Payment Terms: L/C, T/T, Western Union

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: CKFXRS-12II/d, CKFXRS-19II/d, CKFXRS-35II/d
  • Heat Temperature: 50-70°C
  • Heat Source: Air-source
  • Application: Villa Family, Sauna and Swimming Pool, Hotels, Factory Hospital, Student Apartments, Beauty Salons
  • Rated Heating Capacity: 12kw, 19kw, 36kw,55kw, 75kw, 105kw, 145kw
  • Type: Side Blowing
  • Heat Exchanger: Swep
  • Trademark: KONNEN
  • Origin: China (Mainland)
  • Energy Efficiency Grade: One
  • Work Environment: Low-temperature Heat Pump
  • Heating Type: Circulating Heat
  • Certification: CE, ISO9001, CCC, SASO
  • Compressor: Copeland
  • Cop at Ambient Temp. -25c: 1.8
  • Control System Brand: Konnen
  • Specification: CE
Product Description
EVI air source heat pump with Copeland compressor and tested in our national proved laboratory.
More than 6 months testing for all kinds of conditions, lowest ambient temperature tested -20C.
Use our own control system which allows the best controlling for EVI heat pump in China.
We can sure that our EVI heat pump can reach one of the best performance and COP in China.
Evi Low Temperature Air Source Heat Pump Lowest Working Temp. -25c, Tested in National Proved Laboratory
Evi Low Temperature Air Source Heat Pump Lowest Working Temp. -25c, Tested in National Proved Laboratory
Evi Low Temperature Air Source Heat Pump Lowest Working Temp. -25c, Tested in National Proved Laboratory
AIR TO WATER HEAT PUMP WATER HEATER
AIR SOURCE HEAT PUMP WATER HEATER
EVI AIR SOURCE HEAT PUMP
EVI AIR TO WATER HEAT PUMP
LOW TEMPERATURE HEAT PUMP

A02U series( EVI air source heat pump low temperature type)                                                                                                                                             EVI-150307

EVI3P-S5EVI5P-S5EVI10P-C24EVI15P-C24EVI20P-C48EVI30P-C48EVI40P-C96
Normal conditionHeating capacitykW1219365575105145
Input powerkW2.80 4.40 8.20 12.70 17.10 24.10 33.20 
Input currentA5.30 8.60 14.80 24.20 33.00 45.10 62.50 
COP/4.29 4.32 4.39 4.32 4.39 4.36 4.37 
Nominal  conditionRated heating capacitykW9.50 15.00 30.00 45.00 60.00 90.00 120.00 
Rated input powerkW2.60 4.10 8.10 12.20 16.10 24.50 32.50 
Rated input currentA5.20 8.20 15.30 23.10 30.20 46.00 61.10 
COP/3.65 3.66 3.70 3.68 3.73 3.67 3.69 
Low temperature conditionHeating capacitykW5.50 8.80 17.50 15.30 36.50 52.50 70.00 
Input powerkW2.26 3.65 7.30 6.41 15.10 21.60 29.10 
Input currentA4.29 6.93 13.00 12.10 28.10 40.80 54.80 
COP/2.43 2.41 2.40 2.39 2.42 2.43 2.41 
Maximum input power/currentkW/A3.61/6.925.71/11.2010.62/20.7516.52/32.2322.27/43.3631.38/61242.92/83.62
Rated hot water output temperatureºC55
Maximum hot water output temperatureºC60
Rated hot water produce capacityL/H204.25322.5645967.5129019352580
Power supply3N 380V/50Hz
CompressorTypeFully closed scroll type
Start modeDirectly start
Water side heat exchangerTypeShell & coil(tube) heat exchanger
Water flowM3/h2.1 3.3 6.0 9.5 12.9 18.0 24.9 
Water pressure dropKPa≤50≤55≤60≤60≤65≤65≤65
Pipe sizeDN25253232506565
Middle heat exchangerTypeBrazed plate type heat exchanger
Protections1. High pressure and low pressure protection, 
2. Anti-freezing protection, 
3. High temperature protection, 
4. Too big of the water temperature difference for outlet and inlet protection, 
5. Overload protection, 
6. Lack phase protection, 
7. Reverse phase protection, etc.. 
NoiseDB(A)≤55≤58≤65≤68≤70≤73≤74
Unit dimensionsmm835×410×13301000×1000×18581000×1000×18581000×2050×19001000×2050×19802000×2050×1980
WeightKG1151753554256208551250
Testing condition: 1. Normal condition: dry bulb 20ºC, wet bulb 15ºC; initial water temperature 15ºC, end water temperature 55ºC.
                          2. Nominal condition: dry bulb 7ºC, wet bulb 6ºC; initial water temperature 9ºC, end water temperature 55ºC.
                          3. Low temperature condition: dry bulb -12ºC, wet bulb -14ºC; initial water temperature 9ºC, end water temperature 55ºC.
 
The above parameters may have some differences from the final product because of products updating, so above information is not the provision of any business contract. Please refer to final product lable when buy, or refer to us for any information. Our company keeps the right to interpret.