• Evi Air Source Heat Pump Low Temperature Type for Hot Water +Floor Heating with Ce
  • Evi Air Source Heat Pump Low Temperature Type for Hot Water +Floor Heating with Ce
  • Evi Air Source Heat Pump Low Temperature Type for Hot Water +Floor Heating with Ce
  • Evi Air Source Heat Pump Low Temperature Type for Hot Water +Floor Heating with Ce

Evi Air Source Heat Pump Low Temperature Type for Hot Water +Floor Heating with Ce

Energy Efficiency Grade: One
Heat Temperature: 40-60°c
Work Environment: Low-temperature Heat Pump
Heat Source: Air-source
Heating Type: Circulating Heat
Application: Villa Family
Samples:
US$ 13500/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2010

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
EFH3P-EFH48P
Certification
CE, ISO9001, CCC, SASO, TUV
Product Name
Evi System Air Source Heat Pump for Low Temperatur
Refrigerant
R410A
Compressor
Copeland/SANYO
Rated Heating Capacity
11.5kw
Rated Outlet Hot Water Quantity
204.25L/H
Transport Package
Safe Export Packing
Specification
standard
Trademark
KONNEN
Origin
China
HS Code
8418612090
Production Capacity
3500 Units/Month

Product Description

D03 series( EVI Air source heat pump Hot water use & Space heating)                                                                                            EVI-150307
  EFH3P-S5 EFH5P-S5 EFH10P-C24 EFH14P-C24 EFH20P-C48 EFH30P-C48 EFH48P-C96
Normal condition Heating capacity kW 12  19  36  50  75  105  165 
Input power kW 2.80  4.40  8.20  11.57  17.10  24.10  38.10 
Input current A 5.30  8.60  14.80  23.86  33.00  45.10  72.30 
COP / 4.29  4.32  4.39  4.32  4.39  4.36  4.33 
Nominal  condition Rated heating capacity kW 9.50  15.00  42.00  30.00  60.00  90.00  144.00 
Rated input power kW 2.60  4.10  8.10  11.39  16.10  24.50  39.30 
Rated input current A 5.20  8.20  15.30  21.56  30.20  46.00  73.60 
COP / 3.65  3.66  3.70  3.68  3.73  3.67  3.66 
Low temperature condition Heating capacity kW 5.50  8.80  17.50  24.50  36.50  52.50  84.00 
Input power kW 2.26  3.65  7.30  10.21  15.10  21.60  34.90 
Input current A 4.29  6.93  13.00  18.30  28.10  40.80  65.70 
COP / 2.43  2.41  2.40  2.40  2.42  2.43  2.41 
Space heating standard conditions heating capacity kW 9.00  14.50  28.80  40.32  57.50  86.25  138.00 
Input power kW 2.82  4.61  9.20  12.80  18.30  27.45  43.92 
Input current A 5.33  8.71  17.40  24.36  34.80  52.20  83.50 
COP / 3.19  3.15  3.14  3.15  3.14  3.14  3.14 
Maximum input power/current kW/A 3.61/6.92 5.71/11.20 10.62/20.75 14.86/29.05 22.27/43.36 31.38/61.2 51.5/100.3
Rated hot water output temperature ºC 55
Rated space heating water output temperature ºC 45
Maximum hot water output temperature ºC 60
Rated hot water produce capacity L/H 204.25 322.5 645 903 1290 1935 3096
Power supply 3N 380V/50Hz
Compressor Type Fully closed scroll type
Start mode Directly start
Water side heat exchanger Type Shell & coil(tube) heat exchanger
Water flow M3/h 2.1  6.0  8.9  12.9  18.0  29.9 
Water pressure drop KPa ≤50 ≤60 ≤60 ≤65 ≤65 ≤65
Pipe size DN 25 32 32 50 65 80
Middle heat exchanger Type Brazed plate type heat exchanger
Protections 1. High pressure and low pressure protection,
2. Anti-freezing protection,
3. High temperature protection,
4. Too big of the water temperature difference for outlet and inlet protection,
5. Overload protection,
6. Lack phase protection,
7. Reverse phase protection, etc.. 
Noise DB(A) ≤55 ≤65 ≤68 ≤70 ≤73 ≤78
Unit dimensions mm 835×410×1330 1000×1000×1858 2050x1000x1980 2050x2000x1980
Package Size mm 980*550*1550 1150*1150*2250 2200×1150×2300 2300×2100×2300
Weight KG 115 175 355 425 620 855 1300
Testing condition: 1. Normal condition: dry bulb 20ºC, wet bulb 15ºC; initial water temperature 15ºC, end water temperature 55ºC.
                      2. Nominal condition: dry bulb 7
ºC, wet bulb 6ºC; initial water temperature 9ºC, end water temperature 55ºC.
                      3. Low temperature condition: dry bulb -12
ºC, wet bulb -14ºC; initial water temperature 9ºC, end water temperature 55ºC.
                      4.Heating standard condition: dry bulb temperature 7
ºC, wet bulb temperature 6ºC; Cold water inlet temperature 40ºC,outlet water temperature 45ºC.

 