Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor

Product Details
Customization: Available
Certification: SASO, CCC, ISO9001, CE
Working Medium: R410A
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2010

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

to see all verified strength labels (27)
  • Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
  • Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
  • Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
  • Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
  • Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
  • Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
Find Similar Products

Basic Info.

Model NO.
A02H
Heat Source Type
Air Source Heat Pump
Compressor
Copeland or Panasonic
Capacity
105kw
Functions
Cooling + Heating
Transport Package
Plywood Case
Specification
CE
Trademark
KONNEN
Origin
Zhejiang, China
HS Code
8418612090
Production Capacity
300 Units/Month

Product Description

AIR TO WATER HEAT PUMP FOR COOLING AND HEATING, AIR SOURCE HEAT PUMP FOR COOLING AND HEATING.

Components we use:
* Copeland compressor & Daikin R410a refrigerant refrigerant;
* Stainless steel 304 for all fasteners, for side covers of evaporatorer, stainless steel 304 for casing for option;
* Chinese No.1 brand "ND" shell & tube heat exchanger;
* Japan "Saginomiya"  or "SANHUA" electronic expansion valve;
* World sales No.1 "SANHUA" 4-way valve;
* One way valve for stable cooling;
* Advanced LCD controller, easy for operation;
* Delivery time: 25~35 days;
* Warranty time: 24 months after installation.

WE offer OEM service!

KONNEN NEW FACTORY:
Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
WHY CHOOSE US:
Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
PRODUCT FEATURES:
Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
World famous brands we cooperated for our heat pumps:
Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
Our Projects:
Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor
Heat pump loading:

Air to Water Heat Pump with Two Years Warranty Time and Panasonic Compressor

Parameters:
  CL8s-CA5 CL12s-CA5 CL13-CA5 CL15-CA5 CL18-CA5 CL26-CA10 CL30-CA10 CL38-CA10 CL66-CA20 CL99-CA20 CL132-CA20
Rated cooling capacity kW 12.5  13  15  18  26  30  38  66  99  132 
Rated input power for cooling kW 2.46  3.78  4.06  4.60  5.47  8.15  9.23  11.66  21.57  31.13  40.12 
Rated input current for cooling A 10.94  16.78  7.80  8.83  10.50  15.65  17.72  22.38  41.41  59.77  77.03 
Cooling performance coefficient (EER)  / 3.25  3.31  3.20  3.26  3.29  3.19  3.25  3.26  3.06  3.18  3.29 
Rated heating capacity kW 8.8  13.5  14.5  17  20  28  32  40  72  108  136 
Rated input power for heating kW 2.68  4.12  4.52  5.18  6.27  8.46  9.85  12.12  22.09  33.13  41.72 
Rated input current for heating A 11.92  18.29  8.67  9.95  12.04  16.24  18.90  23.27  42.40  63.61  80.10 
Heating performance coefficient (COP) / 3.28  3.28  3.21  3.28  3.19  3.31  3.25  3.30  3.26  3.26  3.26 
Maximum input power kW 3.49  5.35  5.87  6.74  8.15  11.00  12.80  15.76  28.71  43.07  54.23 
Maximum input current A 15.50  23.78  11.27  12.94  15.65  21.11  24.58  30.25  55.13  82.69  104.13 
Energy regulation % 0, 100 0, 50, 100 0,33,66,
100
0,25,50,
75,100
Power supply 1N 220V/50Hz
(Special power supply for option)
3N 380V/50Hz(Special power supply for option)
Compressor Type Hermetic scroll type
Start mode Directly start(Soft start for option)
Quantity Set 1 1 1 1 1 2 2 2 2 3 4
Water side  Type Shell & coil(tube) heat exchanger
Water flow M3/h 1.38  2.15  2.24  2.58  3.09  4.47  5.16  6.54  11.35  17.03  22.70 
Water pressure drop ≤KPa 45 45 45 45 50 50 50 52 55 60 65
Water connection size DN DN25 DN32 DN65
 Pipe connection Inner thread Flange
Air Side  Exchanger Finned tube heat exchanger
Rated Air flow m3/h 3500 6320 3500 6320 7500 12500 12500 14800 26000 39000 55000
Rated output power of fan motor W 120 250 120 250 370 550 550 750 1100 1500 2200
Air blowing type Horizontal Vertical
Refrigerant Throttle type Electronic expansion valve
Quantity KG 2.1 3.0  3.2 3.6 4.2 3.2×2 3.6×2 4.2×2 9.6×2 9.6×3 9.6×4
Noise DB(A) ≤55 ≤63 ≤63 ≤63 ≤66 ≤66 ≤66 ≤68 ≤72 ≤75 ≤78
Dimension mm 1100x410x1550 990x990x1800 1000x2050x1850
Wooden case package dimensions(L*W*H) mm 1146x456X1712 1046x1046x1968 1056x2106x2018
Net weight kg 115 135 170 185 190 310 335 360 650 820 940
Gross weight kg 130 150 185 200 205 340 365 390 685 855 975
Testing condition:1. Standard cooling working condition: dry bulb temperature 35ºC, water input 12ºC, water output 7ºC.
                                2. Standard heating working condition: dry bulb temperature 7ºC, wet bulb 6ºC; water input 40ºC, water output 45ºC.
The above parameter are for single module, could be grouped according to requirements. 
The above parameters are based on Refrigearnt R410A, for parameters based on other refrigerant please contact us.
The above parameters may have some differences from the final product because of products updating, so above information is not the provision of any business contract. Please refer to final product label when buy,or refer to us for any information.Our company keeps the right to interpret.

AIR TO WATER HEAT PUMP, AIR SOURCE HEAT PUMP, AIR TO WATER HEAT PUMP FOR COOLING AND HEATING, AIR SOURCE HEAT PUMP FOR COOLING AND HEATING, AIR WATER HEAT PUMP.

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier