Customization: | Available |
---|---|
Heat Temperature: | 50-70°C |
Work Environment: | Common Heat Pump |
Still deciding? Get samples of US$ 1200/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
* Panasonic compressor OR Copeland compressor with R134a refrigerant, |
* Stainless steel 304 for all fasteners, for side covers of evaporator; |
* Preservative oil for copper tubes and all important part of cabinet; |
* Chinese No.1 brand "ND" shell & tube heat exchanger; |
* Japan "Saginomiya" or "Sanhua" electronic expansion valve; |
* "Sanhua" 4-way valve; |
* "Schneider" AC contactor & Relay |
* LCD controller; |
* Delivery time: 20~25 days; |
* Payment term: T/T 30% in advance and T/T 70% before delivery; |
* Warranty time: 24 months after delivery. |
A03H (High temperature air source heat pump water heater circulation type) HT-150307 | |||||||||||
HT3P-T3 | HT5P-T5 | HT7P-T5 | HT10P-C24 | HT14P-C24 | HT20P-C48 | HT24P-C48 | HT30P-C48 | HT48P-C96 | |||
Rated heating capacity | kW | 8 | 13.5 | 18 | 26 | 35 | 55 | 65 | 80 | 130 | |
Rated input power | kW | 2.19 | 3.66 | 4.96 | 7.11 | 9.62 | 14.91 | 17.81 | 21.98 | 35.81 | |
Rated input current | A | 4.14 | 6.92 | 9.37 | 13.55 | 18.17 | 28.17 | 33.66 | 41.54 | 67.69 | |
Maximum input power | kW | 2.74 | 4.58 | 6.20 | 8.89 | 12.02 | 18.63 | 22.26 | 27.47 | 44.77 | |
Maximum input current | A | 5.34 | 8.92 | 12.09 | 17.33 | 23.44 | 36.33 | 43.41 | 53.57 | 87.29 | |
Performance coefficient(COP) | / | 3.65 | 3.69 | 3.63 | 3.65 | 3.64 | 3.69 | 3.65 | 3.64 | 3.63 | |
Rated hot water output temp. | ºC | 75 | |||||||||
Maximum hot water output temp. | ºC | 80 | |||||||||
Rated hot water produce capacity | △t40 | L/H | 172.0 | 290.3 | 387.0 | 559.0 | 752.5 | 1182.5 | 1397.5 | 1720.0 | 2795.0 |
△t60 | L/H | 114.7 | 193.5 | 258.0 | 372.7 | 501.7 | 788.3 | 931.7 | 1146.7 | 1863.3 | |
Power supply | 3N 380V/50Hz | ||||||||||
Compressor | Type | Fully closed scroll type | |||||||||
Start Mode | Directly start | ||||||||||
Quantity | Set | 1 | 1 | 1 | 2 | 2 | 4 | 2 | 3 | 4 | |
Water side heat exchanger | Type | Shell & coil(tube) heat exchanger | |||||||||
Water flow | m3/h | 1.4 | 2.3 | 3.1 | 4.5 | 6.0 | 9.5 | 11.2 | 13.8 | 22.4 | |
Water Pressure Drop | kPa | <50 | <55 | <57 | <60 | <60 | <65 | <65 | <65 | <65 | |
Pipe size | mm | DN20 | DN25 | DN25 | DN32 | DN32 | DN50 | DN50 | DN50 | DN80 | |
Protections | 1. High pressure and low pressure protection, 2. Anti-freezing protection, 3. High temperature protection, 4. Too big of the water temperature difference for outlet and inlet protection, 5. Overload protection, 6. Lack phase protection, 7. Reverse phase protection, etc.. |
||||||||||
Refrigerant | Type | R134a | |||||||||
Throttle Type | Electronic expansion valve | ||||||||||
Quantity | kg | 2.1 | 3.3 | 4.3 | 2.8×2 | 4.1×3 | 3.2×4 | 7.6×2 | 6.2*3 | 7.6×4 | |
Noise | DB(A) | ≤55 | ≤63 | ≤65 | ≤65 | ≤68 | ≤70 | ≤72 | ≤73 | ≤78 | |
Unit Dimension | mm | 700×680× 875 |
860×820× 1080 |
860×820× 1080 |
1000×1000×1858 | 1000×1000×1858 | 1000×2050×1900 | 1000×2050×1900 | 1000×2050×1900 | 2000×2050×1900 | |
Package Dimension | mm | 788x768x940 | 898x898x1140 | 898x898x1140 | 1100x1100x1880 | 1100x1100x1880 | 1080x2130x 1940 | 1080x2130x 1940 | 1080x2130x 1940 | 2028x2220×1940 | |
Net Weight | kg | 100 | 170 | 190 | 310 | 410 | 605 | 650 | 835 | 1250 | |
Testing conditions: | |||||||||||
1. Application side initial water temperature: 15ºC, end temperature 75ºC, max. temperature 80ºC. | |||||||||||
2. Ambient temperature dry bulb 20ºC, wet bulb 15ºC. | |||||||||||
The above parameters are based on Refrigearnt R134a, for parameters based on other refrigerant please contact us. | |||||||||||
The above parameters may have some differences from the final product because of products updating, so above information is not the provision of any business contract. Please refer to final product label when buy, or refer to us for any information. Our company keeps the right to interpret. |